Description
Sauermann Si-1801 23′ Centrifugal Tank Pump 120V
The Si-1801 23′ pump is capable of evacuating 132 gph, and is suitable for condensing boilers & furnaces, industrial refrigeration cases, and air conditioning units.
Easy Install
- Pump can be floor mounted, attached to a wall or hung from a ceiling.
High Resistance
- Oil and acid resistant float.
- Mechanical structure resistant to shocks.
Versatile
- Easily removable tank for simple maintenance and algae control.
- Reversible pump allows mounting on either side of the installation, and the choice of which side the water exits the pump.
Easy Connection
- New quarter turn, easily removable check valve,
designed to facilitate 3/8” i.d. hose plug in. - 4 inlet holes 13/16” O.D.
Features and Benefits
- Can endure acidic condensate pH > 2.5
- Oil & acid resistant flow
- Low sound level: ≤ 45 dBA
- Easily removable tank for simple maintenance
- Discharges condensate up to 23′
Kit Content
- One-piece centrifugal pump with 1/2 gal. tank.
- Integrated barb end check valve 3/8” o.d. (10 mm).
- 6′ power cord.
- Safety switch wires (1′ bare ends).
- Adaptor: 5/8″ i.d., 3/4″ i.d, 1″ i.d., 1 1/4″ i.d.
- 2 screws & 2 wall anchors.
Sauermann #Si-1801 23′ Specifications
- Max Flow Rate: 132 gph 500 l/h
- Shut-Off Head: 23ft @ 60Hz
- Sound Level: 45 dBA according to EN ISO 3744 (Measured at LNE lab, pump operating w/water, out of application)
- Power Supply: 120 V ~ 60 Hz – 85 W – 1.45A
- Detection Levels: On: 2 3/32” • Off: 1 21/32” • Safety: 2 1/2”
- Safety Switch: NC 4A resistive – 42 V peak
- Max Condensate Temperature: 150° F / Short Peak 176° F – 1m
- Max Condensate Acidity: pH > 2.5 (Gas Condensing Boilers)
- Thermal Protection: 248° F auto-reset
- Operating Conditions: 120V – 30%: 3s ON – 7s OFF
- Pump Dimensions: 11″L x 5 3/16″W x 6 5/7″H
- Safety Standards: UL / CSA certified by Intertek
- RoHS & WEEE Directives: Compliant
- Packaging: 6.2 lbs (115/8″ L x 5 5/16″W x 9 7/8″H)
- Country of Origin (subject to change): United States
Restrictions and Compliance
- WARNING: Risk of electric shock. This pump is supplied with a grounding cable and a grounding attachment plug. To reduce the risk of electric shock, ensure that the pump is connected only to a suitable grounding device.
- WARNING: This pump has been designed for use with water only.
- WARNING: This pump has been designed for indoor use only. It must not be immersed and/or placed in areas of high humidity or where the ambient temperature conditions are below freezing.
Product Bulletin Download
Technical Data Sheet Download
3D File Download
Reviews
There are no reviews yet.